To connect the Aquamonix Emflux i500 to the FerIT it needs to be configured with the following MODBUS settings

|  |  |
| --- | --- |
| **Setting** | **Value** |
| Connection Type | RS485 |
| MODBUS Address | 1 |
| Baudrate | 9600 |
| Parity | None |
| Stop Bits | 1 |

To run RS485 with the i500 flowmeter, three jumper switches need to be correctly configured, 2 on the main board and 1 on the MODBUS card.

On the main board

- The top jumper is set to ON
- The bottom jumper is set to OFF

On the MODBUS card the jumper is set to OFF